Plate Filter(Flat)
Describe
Product Advantages
1、Space-Saving
2、Easy to install
3、Stable structure
Application
Primary filtration for central air conditioning systems and clean air conditioning systems, extending the service life of downstream filters.
Operating Environment
Temperature Resistance Performance:70℃
Moisture Resistance Performance:100%RH
Performance Parameters
| Model |
Dimension W×H×D (mm) |
Filter Class EN779 |
Rated Airflow (m³/h) |
Initial Resistance (Pa) |
Recommended Final Resistance (Pa) |
| P1G2-A20-592x592x20-T2-W20 | 592x592x20 | G2 | 1800 | 45 | 200 |
| P1G2-A20-290x592x20-T2-W20 | 290x592x20 | G2 | 1800 | 45 | 200 |
| P1G3-A20-592x592x20-T2-W20 | 592x592x20 | G3 | 1800 | 50 | 200 |
| P1G3-A20-290x592x20-T2-W20 | 290x592x20 | G3 | 1800 | 50 | 200 |
Note: Special sizes or specifications can be customized according to customer requirements